Permit Number: TC-COM-0926-01560
Parcel: 13216600A

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0926-01560
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2026 Commercial Electrical Standard APPROVED
09/28/2026 Site Engineering Standard APPROVED
10/09/2026 Commercial Mechanical Standard NOT REQUIRED
10/09/2026 Commercial Plumbing Standard NOT REQUIRED
10/01/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
10/09/2026 Water - PDSD Standard NOT REQUIRED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
10/09/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01560
ADDRESS/PARCEL: (4004 S PARK AV Unit:BLDG 2 TUCSON, AZ 85714)
Submit your revised drawings along with a ***detailed response letter***, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. ACCESSIBLE EV CHARGER:
a. Accessible EV charging stations shall comply with IBC 1107.2. IBC 1107.2.1 Not less than 5 percent of vehicle spaces on the site served by electrical vehicle charging systems, but not fewer than one for each type of electric vehicle charging system, shall be accessible vehicle spaces. Locate and label this accessible stall on Sheet E2.0 Equipment and Conduit Plan.
b. IBC 1107.2.2 Vehicle space size. Accessible vehicle spaces shall comply with the requirements for a van accessible parking space that is 132 inches minimum in width with an adjoining access aisle that is 60 inches minimum in width. Locate and label this accessible stall on Sheet E2.0 Equipment and Conduit Plan with dimensions and illustrate on the drawing how impediments are removed complying to accessibility per ICC A117.1. Provide an enlarge stall drawing to illustrate this.
2. Please resubmit.
10/12/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Jeffrey W. Cassidy, Planner I
Planning & Development Services Department – Current Zoning Review Section, Commercial

PROJECT:
TC-COM-0926-01560 – Commercial – Installation of (15) Level 2 EV chargers & (1) Level 3 EV charger
4004 S PARK AV BLDG 2 TUCSON, AZ 85714 (I-1 Zoning)
Commercial Building Plan Review – 1st Review

TRANSMITTAL DATE:
October 12, 2026

1. COMMENT: Accessible EV charging stations shall comply with IBC 1107.2. IBC 1107.2.1 Not less than 5 percent of vehicle spaces on the site served by electrical vehicle charging systems, but not fewer than one for each type of electric vehicle charging system, shall be accessible vehicle spaces. Locate and label this accessible stall on Sheet E2.0 Equipment and Conduit Plan.

2. COMMENT: Vehicle space size. Accessible vehicle spaces shall comply with the requirements for a van accessible parking space that is 132 inches minimum in width with an adjoining access aisle that is 60 inches minimum in width. Locate and label this accessible stall on Sheet E2.0 Equipment and Conduit Plan with dimensions and illustrate on the drawing how impediments are removed complying to accessibility per ICC A117.1. Provide an enlarge stall drawing to illustrate this.

3. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:

4. COMMENT: Corrected commercial building permit.

5. COMMENT: Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments.

To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home .

Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/old-pdfs/double-old/resubmittals.pdf

If you have any questions about this transmittal, please contact jeffrey.cassidy@tucsonaz.gov

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code .
09/22/2026 PDSD Application Completeness Express REVIEW COMPLETED