Permit Number: TC-COM-0926-01550
Parcel: 11460041C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0926-01550
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2026 Site Zoning Standard APPROVED
11/05/2026 Water - PDSD Standard APPROVED
11/02/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
10/20/2026 Site Engineering Standard NOT REQUIRED
11/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/09/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit a complete set of revised/corrected documents and a written response addressing each review comment and explaining how it was resolved. The original submittal was incomplete, and additional comments may be issued upon subsequent review.
Please email me with any questions regarding the comments below: mark.masek@tucsonaz.gov
1. Please revise and resubmit a complete set of construction documents bearing the current, original seal, signature, and date of each licensed design professional responsible for their preparation. All documents shall comply with AZBTR requirements and the 2024 IBC. Plans with expired, missing, or invalid professional seals will not be accepted for permit review. Code References:
2024 IBC Section 107.1 – General
Arizona Board of Technical Registration (AZBTR) – Professional document sealing, signature, and date requirements.
For example, Registered Architect Robert Wesley with seal # C33978 could not be found in the AZBTR licensee search. Both Seals were not signed by the licensed registrants.
2. Please provide the structural design, calculations and the construction drawings and details prepared by an Arizona Licensed registrant with next submittal. IBC 107.2.1
3. Please provide a list that includes all the drawing sheets and their corresponding sheet labels in this permit’s scope. IBC 107.2.1
4. Please provide, construction details, referenced callouts and detailed construction drawings. IBC 107.2.1 For example sheet A105 has keynote numbers, refers to Sheet A-02 and the information cannot be found.
5. Please indicate the exterior finish on sheet A104. IBC 107.2.1
6. Please update detail drawings on sheet A103 to show construction conditions, reference callouts, and provide details. IBC 107.2.1
7. The floor plan has referenced callouts for located on sheet A2.0, however sheet A2.0 in not included in the set of drawings. IBC 107.2.1
8. Pleas provide dimensioned drawings including elevations, for new breakroom showing compliance with 2017 ICC A117.1

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
11/02/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0926-01550 (7359 E TANQUE VERDE RD TUCSON, AZ 85715)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Clarify if this is a new gas line and new gas meter. Provide electrical grounding bond to all new metallic gas piping, Metallic gas lines must be bonded and not be used as the primary grounding method, [NEC 250.52(B)(1)].
11/05/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01550
ADDRESS/PARCEL: 7359 E TANQUE VERDE RD TUCSON, AZ 85715

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please provide venting details for the tankless water heater. If the unit is intended to be installed as a direct-vent appliance, clearly illustrate the installation on the drawings, including the combustion air intake, exhaust vent routing, and terminations. Reference: Section 503, IFGC 2024.
11/05/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01550
ADDRESS/PARCEL: 7359 E TANQUE VERDE RD TUCSON, AZ 85715

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please provide the specifications and listing information for the proposed water heaters (tankless gas water heater and electric water heater). Reference: Sections 303.2 and 501.5, IPC 2024, and Section 107.2.1, IBC 2024.
2. Please show all other gas-fired appliances connected to the gas meter as well and the total gas demand seen by the meter. Verify the existing gas piping system is adequately sized for the new tankless water heater. Reference: Section 402, IFGC 2024.
3. Please show how each new water heater connects to the existing water distribution system. Reference: Section 107.2.1, IBC 2024.
4. A new electric water heater is identified in the keynotes on Sheet A102. Please show the associated water distribution piping and a detail of the water heater installation. Reference: Section 107.2.1, IBC 2024.
11/10/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
10/20/2026 PDSD Application Completeness Express REVIEW COMPLETED