Permit Number: TC-COM-0926-01548
Parcel: 10321029W

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0926-01548
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/23/2026 Commercial Mechanical Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01548
ADDRESS/PARCEL: 2250 W IRONWOOD HILL DR TUCSON, AZ 85745

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Previous comment not addressed. [Initial comment - Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Section C403.3.1, IECC 2024)...]
a. Please provide heating and cooling load calculations to verify that the proposed HVAC equipment is properly sized for the space. Reference: Section C403.1.1 and C502.3.3, IECC 2024.
b. Please label each proposed HVAC unit on the site plan.
09/22/2026 Addressing Validation REVIEW COMPLETED
09/22/2026 PDSD Application Completeness Express REVIEW COMPLETED