Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0926-01548
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/23/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/23/2026 | Commercial Mechanical Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0926-01548 ADDRESS/PARCEL: 2250 W IRONWOOD HILL DR TUCSON, AZ 85745 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov COMMENTS: 1. Previous comment not addressed. [Initial comment - Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Section C403.3.1, IECC 2024)...] a. Please provide heating and cooling load calculations to verify that the proposed HVAC equipment is properly sized for the space. Reference: Section C403.1.1 and C502.3.3, IECC 2024. b. Please label each proposed HVAC unit on the site plan. |
||
| 09/22/2026 | Addressing Validation | REVIEW COMPLETED | |||
| 09/22/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |