Permit Number: TC-COM-0926-01542
Parcel: 13705141B

Address:
5048 S 12TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0926-01542
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/15/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0926-01542 (5048 S 12TH AV TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Clarify if there is any existing electrical service meters on the site, additional service meters must meet the requirements of NEC 230.2 (Number of Services). Or is this a replacement of an existing meter/service entrance?
2. Provide conductor and conduit sizing and type from Main Panel A to the two subpanels. NEC chapter 3. Include minimum burial depth of 2 feet under vehicle accessible locations.
3. Update Main Panel A schedule to show the correct wire size and breaker sizes to match the given Riser diagram.
4. Provide a power plan for the Existing utility building as well.
5. Clearly define the use of the space in the buildings. GFCI protection is required if the space is used for vehicle repair or servicing. NCE 210.8(B).