Permit Number: TC-COM-0926-01542
Parcel: 13705141B

Address:
5048 S 12TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0926-01542
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/18/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0926-01542 (5048 S 12TH AV TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Please provide updated plans that show compliance with the currently adopted codes. You cannot use plans that show compliance with the 2017 NEC or 2018 IBC. You also cannot add new information to plans previously sealed by a Registrant.
2. The provided plans were reviewed previously and had the following review comments that were not addressed. Please address all comments:

Ref; Electrical Line Diagram.

1. Show the new electrical service riser conduit size and conductor quantity, sizes and types.

2. Show the AIC ratings for the service and sub-panels.

3. Show the existing underground conduit sizes and types for the panel feeders.

Ref; Power and Lighting, Site Plan.

1. Are the receptacles, fans and luminaires new to be installed per this project or are they existing?

2. If the work bench area is not enclosed provide WP/ GFI protected outlets and devices, per NEC 210.8(B).

3. If the work areas or building(s) are not totally enclosed where lighting is installed, provide full compliance with the 2012 City of Tucson Outdoor Lighting Code. Include any other exterior lighting on the parcel.

4. What about the Existing Utility Building? Show all electrical devices and lighting connecting to the new sub-panel ā€˜C’.

5. Provide compliance with the 2018 IECC if applicable.
09/18/2026 PDSD Application Completeness Express REVIEW COMPLETED