Permit Number: TC-COM-0926-01535
Parcel: 115081890

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0926-01535
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/15/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0926-01535 (301 W HELEN ST Unit:UNIT 7 TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Provide an electrical riser diagram, NEC 230.9. Include underground service entrance conductors/conduit.
a. Show each meter and address/unit associated with each meter.
b. Show bus bar or equipment rating and AIC ratings of the new equipment.
c. Provide sizing and other info as needed to verify code compliance.
2. Notate the grounding and bonding method, including water line bonding, NEC 250.20(B), 250.24, 250.30(A)(1).
3. Provide Service Surge Protection per NEC 230.67(D). All downstream dwelling units require surge protection when replacing the service equipment.
4. Provide the rating of the equipment being replace, per Ariz. Admin. Code § R4-30-302 - Electrical Plans: A registrant shall prepare and submit drawings and specifications for a an addition or modification to an existing electrical system provided the service and associated electrical feeders exceeds 600 amperes 120/240 volts, single phase or 225 amperes 120/208 volts, three phase and the fault current exceeds 10,000 amperes.
5. Provide plans prepared and sealed by a qualified Registrant per Ariz. Admin. Code § R4-30-302.