Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0926-01532
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2026 Site Zoning APPROVED
09/18/2026 Site Engineering NOT REQUIRED
10/05/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/02/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. This project constitutes an alteration to a commercial building. Please provide complete architectural and structural construction documents, including structural calculations, prepared, signed, and sealed by design professionals licensed to practice in the State of Arizona. Reference: Section 107.1, IBC 2024, City of Tucson Commercial Submittal Requirements, and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Please show the maneuvering space at each door and the turning space in the Spa room on the plans. 2017 ICC A117.1 304.3.1.2 & 404.2.3.3
3. Please revise the plans to provide at least one accessible changing station. IBC 1110.17
A. The accessible changing rooms shall meet the technical requirements of 2017 ICC A117.1 Section 8 to include
803.2 Turning space.
A turning space shall be provided within the room
803.4 Benches.
A bench complying with Section 903 shall be provided within the room.
803.5 Coat hooks and shelves.
Coat hooks provided within the room shall accommodate a forward reach or side reach complying with Section 308. Where provided, a shelf shall be 40 inches minimum and 48 inches maximum above the floor.
Additionally, the doorway is required to have a minimum clear width of 32”. 2017 ICC A117.1 404.2.2

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
09/24/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0926-01532 (2706 N SILVERBELL RD Unit:BLDG 3 UNIT 3130 TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide an electrical plan showing any/all electrical work. Plans shall include but may not be limited to items below and as necessary for the actual scope of work:
3. Electrical demo plans.
4. Provide an electrical panel schedule and designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
5. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40.
6. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
7. Provide GFCI per NEC 210.8(B) and (D).
10/02/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01532
ADDRESS/PARCEL: 2706 N SILVERBELL RD Unit:BLDG 3 UNIT 3130 TUCSON, AZ 85745

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide sufficient information to demonstrate that the dryer installation complies with the requirements of Section 504 of the 2024 IMC. Revise the plans as necessary. Reference: Section 504, 2024 IMC.
3. Please clearly show the size, routing, and termination of the condensate drains from the new units. Reference: Section 307.2.1, IMC 2024 as amended by the City of Tucson.
4. Please provide heating and cooling load calculations to justify the heating/cooling capacity of the new units. Reference: Section C403.1.1 and C502.3.3, IECC 2024.
6. Please include all zones in the outdoor air calculation table. Please include the Staff Room, Office, and Spa Room. Reference: Section 107.2.1, IBC 2024.
10/02/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01532
ADDRESS/PARCEL: 2706 N SILVERBELL RD Unit:BLDG 3 UNIT 3130 TUCSON, AZ 85745

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Please clarify whether the water heater and plumbing fixtures are new or existing. The plumbing plan on Sheet P1.0 indicates they are existing, while Sheet P2.0 appears to indicate they are new. Reference: Section 107.2.1, IBC 2024.
3. Please provide the manufacturer’s specifications for the spa bed and demonstrate that they will be installed in accordance with the manufacturer’s instructions. Please also show how the spa beds are protected against backflow. Reference: Section 423, IPC 2024.
4. The plumbing fixture schedule specifies a floor sink, but the floor sink does not appear to be shown on the plumbing plan. Please revise the plans to clarify and update the plumbing fixture schedule as necessary.
5. Please provide water, sewer, and vent isometrics for the sink (P5), refrigerator(P6), and washer(P4). Reference: Section 107.2.1, IBC 2024.
10/05/2026 Fire New Construction REQUIRES RESUBMIT -Please resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
10/02/2026 Water - PDSD REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01532
ADDRESS/PARCEL: 2706 N SILVERBELL RD Unit:BLDG 3 UNIT 3130 TUCSON, AZ 85745

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2024 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Please provide the total water demand served by the 1-1/2” water meter. Please adjust the pressure loss calculations as necessary. Reference: Section 107.2.1, IBC 2024.
09/18/2026 PDSD Application Completeness Express REVIEW COMPLETED