09/23/2026 Commercial Electrical APPROVED Approved with comments added to plans:
Provide GFCI protection for all receptacles and appliance outlets in laundry area per NEC 210.8(B) & 210.8(D).
09/29/2026 Site Zoning APPROVED
10/01/2026 Water - PDSD APPROVED
09/18/2026 Site Engineering NOT REQUIRED
10/02/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/02/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.

Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. This is a Commercial project requiring all plans to be sealed and signed by an Architect or Engineer registered in the State of Arizona. accordance with SECTION 107 of the 2024 IBC and the PDSD Commercial Building Plan Submittal Requirements.
2. Sheet A0.1: Building Data – Please up date construction type to indicate llA or llB IBC Section 602.
3. Sheet A0.1: Building Codes - Please remove the 2024 International Residential Code and add the following to the Building Codes.
2024 International Existing Building Code (IEBC), where applicable
2017 ICC A117.1 Accessible and Usable Buildings and Facilities (referenced standard)
2024 International Fire Code (IFC)
2024 International Fuel Gas Code (IFGC)
2018 International Energy Conservation Code (IECC)
City of Tucson Local Amendments to the adopted codes
The current adopted codes and local amendments are available on the City of Tucson Planning and Development Services Department website.
4. Sheet A0.1: Special Inspection Types – Please revise to list the required Special Inspections for this project. IBC 107.2.1
5. Sheet A0.1: Sheet Index -Please revise the sheet index to ensure it includes all sheets in the plan set and that the titles and numbering match the corresponding sheet labels. Provide a complete and consistent index for the entire set. Per IBC Section 107.2.1. For example, sheets A8.0 & P0.1 are listed in the index but not included in the construction drawings. Conversely, sheets A1.0, E0.2, E2.0, M1.1, M1.2, M2.1, M3.1, M3.2, & P4 are included in the construction drawings, but they are not listed in the sheet index.
5. Sheet A0.2: Please revise the calculations for Occupant load, Travel distance, Exiting and ADA seating to reflect the design occupant load for this permit. IBC 107.2, 1004.5, 1017
The occupant load factors for the business areas would be 150sf per person gross and for the waiting area we use 15 SF net. That said the occupant load is close to you total so 21 will work. IBC Table 1017.2 allows 300 feet for exit access travel distance in sprinkled buildings.
Adjust the required and allowable exiting widths and accessibility seating, at least 1,so all number match and all information is consistent.
6. Sheet A1.1, Details 3 & 8 – Grab Bars: Revise grab bar dimensions to comply with 2017 ICC A117.1 §§609.4.2, 604.5.1, Fig. 609.4.2. Provide dimensions verifying:
Horizontal side-wall bar: 33–36" AFF to top and 54" min. from rear wall.
Vertical bar: 39–41" from rear wall to centerline. Current dimensions do not demonstrate compliance.
7. Please amend the plans to show that all through-penetrations, membrane penetrations and joints of fire-resistance-rated assemblies are protected with approved firestopping systems. Provide detail drawings on the plans identifying the specific UL-listed (or equivalent) firestopping systems for pipe, conduit, and duct penetrations through rated walls, floors, and ceilings (e.g., putty pads, firestop sealants, collars, or sleeves, as applicable). IBC Sections 714 & 715 For example, how are the plumbing floor penetrations fire stopped?
8. Please provide existing/demo floor plans IBC 107.2.1
9. Please provide complete wall assembly for the partition walls to include but not be limited to; stud sizes and type wall coverings and anchorage to the floor. IBC 107.2.1


Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
10/01/2026 Commercial Mechanical REQUIRES RESUBMIT 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified heat pump. Reference: Section C403.1.1 and C502.2.3, IECC 2024.
2. The proposed HVAC system recirculates air throughout all of the occupancy types in the suite. Recirculation of air from a beauty salon to other occupancies is prohibited. Reference: Section 403.2.1 (3), IMC 2024.
3. Show the required ventilation flowrate on the mechanical plan, as noted on the Split System Heat Pump Schedule.
4. If the outdoor unit is located in an accessible area, secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.9, IMC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
10/01/2026 Commercial Plumbing REQUIRES RESUBMIT Show how the temperature of the water supply to the scalp sinks is controlled to prevent scalding. Reference: Section 607.1 and 607.1.2, IPC 2024..
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
10/01/2026 Fire New Construction REVIEW COMPLETED
09/17/2026 PDSD Application Completeness Express REVIEW COMPLETED