Permit Number: TC-COM-0926-01524
Parcel: 10511061P

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0926-01524
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2026 Commercial Electrical Standard APPROVED
10/07/2026 Commercial Mechanical Standard APPROVED
10/07/2026 Commercial Plumbing Standard APPROVED approved with comment
10/07/2026 Site Zoning Standard APPROVED
10/07/2026 Water - PDSD Standard APPROVED
09/25/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
09/21/2026 Site Engineering Standard NOT REQUIRED
10/08/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/08/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0926-01524
ADDRESS/PARCEL: (4500 N ORACLE RD Unit:UNIT 178 TUCSON, AZ 85705)
Submit your revised drawings along with a ***detailed response letter***, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. SHEET T-001 KEY MAP: Show the location of the public restroom and drinking fountain on this key map. Provide the distance between the restroom and this mercantile space. IBC 2902.5 and IBC 2902.3.4
2. SHEET T-001 PROJECT DATA: Construction Classification – Please confirm whether a IIA or IIB.
3. SHEET LS-100 LIFE SAFETY PLAN, EGRESS THROUGH INTERVENING SPACE: Egress through intervening spaces. IBC 1016.2
Exception 2 Means of egress are not prohibited through stockrooms
in Group M occupancies where all of the following are met.
2.1 The stock is of the same hazard classification as that
found in the main retail area.
2.2 Not more than 50 percent of the exit access is
through the stockroom.
2.3 The stockroom is not subject to locking from the
egress side.
2.4 There is a demarcated, minimum 44-inch-wide aisle
defined by full- or partial-height fixed walls or similar
construction that will maintain the required width and lead
directly from the retail area to the exit without
obstructions.
Please clearly show the storage racks/shelves & the demarcated aisle with dimension & marking on the floor such as paint stripes, etc
4. SHEET A-100 TOILET ROOM: The turning space shall be a circular space with a 67-inch minimum diameter. ICC A117.1 sec 304.3.1.1 Please make the necessary correction.
5. SHEET A-500 CASHWRAP: The tops of work surfaces shall be 28 inches min & 34 inches max above the floor per ICC A117.1 sec 902.4.
Sec 306.3.3 Knee clearance shall be 11 inches min in depth at 9 inches above the floor, and 8 inches min in depth at 27 inches above the floor.
Sec 306.2.4 Additional toe clearance space extending greater than 6 inches beyond the available knee clearance at 9 inches above the floor.
Sec 306.3 Knee clearance shall be 30 inches min in width.
904.3.2 Parallel approach, the counter surface 36 inches min length.
904.3.3 Forward approach, the counter surface 30 inches min length.
Please comply to all of the above requirements. Please make the necessary correction.
6. SHEET A-501 SHELVINGS: SUBMIT SHELVING SHOP DRAWINGS. THESE RACKS ARE CONSIDERED HIGH PILE STORAGE, PLEASE PROVIDE DETAIL DRAWING AS TO HOW THEY ARE ANCHORED TO THE FLOOR. SPECIAL INSPECTION SHALL BE REQUIRED.
Please provide a special inspection certificate with Part A, and Part B completed with next submittal. Special Inspection(s) Required (Provide table specific to the project) IBC 1705 This form is available in:
a. https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-development-services/documents/special_inspection_certificate.pdf
b. Ensure that Part B is sealed/signed/dated by the special inspector in charge. Ensure to use Special Inspectors who are active in the approved list of special inspectors. They are available in the following links:
i. special-inspectors-by-name.pdf (orovalleyaz.gov)
ii. https://content.civicplus.com/api/assets/e426f390-7bd6-4c47-9bc1-357282083afd
iii. https://www.phoenix.gov/pddsite/Documents/TRT/dsd_trt_pdf_00870.pdf
7. Please resubmit.
10/08/2026 Fire New Construction Standard REVIEW COMPLETED
09/17/2026 PDSD Application Completeness Express REVIEW COMPLETED