Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0926-01466
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/10/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/10/2026 | Commercial Plumbing Express | REQUIRES RESUBMIT | 1. The City of Tucson has adopted the 2024 editions of the IBC, IRC, IMC, IPC, IFGC, IEBC, IFC, and the 2023 edition of the NEC. The controlling document for LP-gas storage and piping outside of the building is NFPA 58-2024. 2. Provide the anticipated gas load in BTUH. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 09/08/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |