Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0926-01435
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2026 | Commercial Building | APPROVED | |||
| 09/09/2026 | Commercial Electrical | APPROVED | |||
| 09/14/2026 | Commercial Plumbing | APPROVED | |||
| 09/16/2026 | Site Zoning | APPROVED | |||
| 09/14/2026 | Water - PDSD | APPROVED | |||
| 09/10/2026 | Site Engineering | NOT REQUIRED | |||
| 09/16/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/14/2026 | Commercial Mechanical | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0926-01435 ADDRESS/PARCEL: 6651 E TANQUE VERDE RD TUCSON, AZ 85715 Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov. COMMENTS: 1. Please provide an air balance schedule showing the total supply and exhaust airflow quantities for the building. Demonstrate that the proposed HVAC systems maintain the 150 CFM net positive building pressure. Reference: Section 508.1.3, IMC 2024. |
||
| 09/09/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 09/04/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |