Permit Number: TC-COM-0926-01430
Parcel: 10309068B

Review Status: Approved

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0926-01430
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2026 Commercial Electrical Express APPROVED Approved with Commetns:
NEC 230.95 Ground-Fault Protection of Equipment.


Ground-fault protection of equipment shall be provided for solidly grounded wye electric services of more than 150 volts to ground but not exceeding 1000 volts phase-to-phase for each service disconnect rated 1000 amperes or more. The grounded conductor for the solidly grounded wye system shall be connected directly to ground through a grounding electrode system, as specified in 250.50, without inserting any resistor or impedance device.
09/02/2026 Bldg Permits - Post Review Express REVIEW COMPLETED
09/02/2026 PDSD Application Completeness Express REVIEW COMPLETED