Review Status: Approved
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0926-01430
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/02/2026 | Commercial Electrical Express | APPROVED | Approved with Commetns: NEC 230.95 Ground-Fault Protection of Equipment. Ground-fault protection of equipment shall be provided for solidly grounded wye electric services of more than 150 volts to ground but not exceeding 1000 volts phase-to-phase for each service disconnect rated 1000 amperes or more. The grounded conductor for the solidly grounded wye system shall be connected directly to ground through a grounding electrode system, as specified in 250.50, without inserting any resistor or impedance device. |
||
| 09/02/2026 | Bldg Permits - Post Review Express | REVIEW COMPLETED | |||
| 09/02/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |