Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/23/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1 Please update the plans so the doors serving a space with ≥ 50 persons swing in the direction of egress travel. IBC 1010.1.2.1
2. Please note or otherwise indicate the doors serving a space with ≥ 50 persons in A occupancies have panic hardware. IBC 1010.1.10
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson