Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL FENCE/WALL v.1
Permit Number - TC-COM-0925-01776
Review Name: COMMERCIAL FENCE/WALL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/13/2025 | Commercial Building | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0925-01776 ADDRESS/PARCEL: (6901 E BROADWAY BL TUCSON, AZ 85710) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. COMMENTS: 1. Existing Wall(s) a. Provide drawings illustrating waterproofing of existing building walls, protected from moisture/water infiltration. This to address the condition such as shown on detail 4/A-3 section thru planer with the note, “existing building wall”. 2. Walls over 7 ft. Submit structural calculation and detail drawings sealed/signed/dated by a licensed Arizona structural engineer. a. Please submit for wall such as shown on detail 4/A-4 which shows walls that are 8 ft tall from the top of the footing. b. Please submit for wall such as shown on detail 4/A-4 which shows walls that are 9 ft tall from the top of the footing. 3. Code Violation CE-VIO0625-02698 a. RWOP : Installed new electrical lines and constructed an office without the proper permits i. Please submit for a building permit for the above. ii. Please email me at Justin.Eder@tucsonaz.gov once this is done. On your response document, please add as well a line indicating that the above has been submitted for review/approval. 4. Please resubmit. Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976 |
||
| 09/30/2025 | Site Engineering | REQUIRES RESUBMIT | Permit: TC-COM-0925-01776 Location: 6901 E BROADWAY BL Review Date: 9/30/2025 Site Engineering Comments: 1. Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf. 2. Site Engineering will be unable to approve permit TC-COM-0925-01776 until the associated development package is submitted for this development and is approved by all reviewers. Per UDC Article 3.3.3.G.2.c If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 10/21/2025 | Site Zoning | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Bobby Parsons Zoning Section Review PROJECT: TC-COM-0925-01776 6901 E. Broadway Blvd. Tucson, AZ 85710 Walls, gates, landscaping, electrical REF: CE-VIO0625-02698 (1st Review) TRANSMITTAL DATE: 10/21/2025 The site is in the C-2 zone (UDC 4.7.21). Multifamily is a permitted use in the C-2 zone. Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed. 1. Comment: Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf. Site zoning is unable to approve this building permit until the DP has been approved by all reviewers. 2. Comment: Additional comments may be forthcoming based on responses to zoning comments and plans submitted. If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov. |
||
| 09/29/2025 | PDSD Application Completeness Express | REVIEW COMPLETED | This permit is for the fence/wall only. |