Permit Number: TC-COM-0925-01770
Parcel: 111051560

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0925-01770
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2025 Commercial Mechanical Standard APPROVED
11/10/2025 Site Zoning Standard NOT REQUIRED AC work ONLY
11/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/14/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0925-01770
ADDRESS/PARCEL: (3054 N SPARKMAN BL TUCSON, AZ 85716)

COMMENTS:
1. Code Violation CE-VIO1123-06525
a. Smoke Detectors, Windows, doors, water leak on roof from cooler, water leaking though roof to ceiling in kitchen, Hall and room, water running down walls leaving puddles on floor.
i. Should the above be for this address, please add the proposed repairs drawings to this permit. (NOTE: if the repairs are made without a permit, do include them into this permit in order for them to be made legal.)
ii. Should the above be for another address, please apply for another permit with drawings illustrating the repairs being made. (NOTE: if the repairs are made without a permit, do include them into this New permit in order for them to be made legal.) Email me at Justin.Eder@tucsonaz.gov once the permit has been applied for, this will allow me to verify and to review them for approval.
2. Please resubmit.

Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
10/21/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0925-01770 (3054 N SPARKMAN BL TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide an electrical plan showing any/all electrical work specific to the buildings and site.
Plans shall include (as necessary for scope of work), but may not be limited to items below:
2. Provide electrical load calculations, for the Main Panel showing it can support the additional electrical load, Per NEC 220.40.
3. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
4. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
5. Provide an electrical floor plans and Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.

Additional comments may be forthcoming with complete electrical plans for the building and site.



Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/20/2025 PDSD Application Completeness Express REVIEW COMPLETED