Permit Number: TC-COM-0925-01757
Parcel: 11702192A

Address:
933 N STONE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0925-01757
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2025 Commercial Electrical Standard APPROVED
10/13/2025 Commercial Mechanical Standard APPROVED
10/13/2025 Commercial Plumbing Standard APPROVED
10/07/2025 Site Engineering Standard APPROVED
10/24/2025 Site Zoning Standard APPROVED Associated DP (TD-DEV-0224-00054) has been issued.
10/16/2025 Water - PDSD Standard APPROVED
10/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/13/2025 Commercial Building Standard REQUIRES RESUBMIT Ed Kulik (480) 241-0634 ekulik@willdan.com
1. Sheet a0.0 List the following information on the cover sheet Total Square footage Square footage by Occupy type Total Occupancy number Type of Construction Fire Sprinklers Y or N Fire Alarm Y or N List all required special inspections.
2. Sheet a0.1 Provide a list of all required special inspections on the cover sheet.
3. Sheet a0.1 This review is for Permit Number TC Com 0925-01757 only.
4. Sheet a0.2 Dwelling units and Sleeping units shall comply with IBC Chapter 11, section 1107 and Chapter 10 of ICC A117.1. When there are four or more units.
5. Sheet a2.2 If the front canopy requires a structural repair, it will need to be submitted for plan review. prior to the work being performed.
10/16/2025 Fire New Construction Standard REQUIRES RESUBMIT 1. Sheet a0.1, applicable codes. COT/TFD has adopted the 2024 IFC. Please make correction to applicable codes.
2. Sheet a0.1, proposed use groups. You currently show the coffee shop being classified as A3 then B since it's less than 50. B occupancy is correct however I believe the coffee shop is an A2 which then can be a B.
john.vincent@tucsonaz.gov
5203495581
10/09/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0925-01757 (933 N STONE AV TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
2. List the Lighting Area per OLC (Typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
4. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
5. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

7. Specify any exceptions used.

8. Provide Curfew lighting controls If applicable Per section 403.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/26/2025 PDSD Application Completeness Express REVIEW COMPLETED