Permit Number: TC-COM-0925-01751
Parcel: 10608002G

Address:
855 W PRINCE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0925-01751
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2025 Outdoor Lighting Standard APPROVED
10/16/2025 Water - PDSD Standard APPROVED
10/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/13/2025 Commercial Building Standard REQUIRES RESUBMIT Structural(S) Reviewer
Andrew Frame
aframe@safebuilt.com
Denied
Reason:
Date Completed : 10/13/2025 12:20:41 PM
10/13/2025 Review Requires Resubmittal AFrame:
1. Sheet S100: GEOTECHNICAL REPORT 29-225001-0 PREPARED BY WESTERN TECHNOLOGIES. DATED
MARCH 12, 2025 is referenced. Please provide GEOTECHNICAL REPORT 29-225001-0 PREPARED BY WESTERN
TECHNOLOGIES. DATED MARCH 12, 2025. Please provide GEOTECHNICAL REPORT 29-225001-0 and resubmit
for review.


Building(B) Reviewer
Andrew Frame
aframe@safebuilt.com
Denied
Reason:
Date Completed : 10/13/2025 12:23:01 PM
10/13/2025 Review Requires Resubmittal AFrame:
1. Sheet T2.0-General Building Summary: R-2 Occupancy is the only Occupancy type listed. Sheet T3.0 Shows a B
Occupancy for the office, an A-3 Occupancy for the Gym, Movie Theatre, and Game Room and gather area, and S-2
Occupancy for Storage. Please include these Occupancies on the General Building Summary on Sheet T2.0 and
resubmit for review.
2. Sheet T2.0: GA file WP 3661 is referenced for Corridor Wall construction. Please provide full /complete GA file WP
3661 details on plans and resubmit for review.
3. Sheet T2.0: UL L521 is referenced for Floor and Ceiling construction. Please provide full /complete UL L521 details on
plans and resubmit for review.
4. Sheet S100: GEOTECHNICAL REPORT 29-225001-0 PREPARED BY WESTERN TECHNOLOGIES. DATED
MARCH 12, 2025 is referenced. Please provide GEOTECHNICAL REPORT 29-225001-0 PREPARED BY WESTERN
TECHNOLOGIES. DATED MARCH 12, 2025. Please provide GEOTECHNICAL REPORT 29-225001-0 and resubmit
for review.
5. Sheet A2.0-Wall Types: 7: UL U415 SYSTEM B is referenced for 2 Hour Rated Shaft Wall Construction. Please
provide full /complete UL U415 SYSTEM B details on plans and resubmit for review.
6. notations from plans if no elevator is to be installed and resubmit for review.
7. Sheets A9.1, A2.0, A2.1, A2.2, A2.3, 2.4, and A2.5: Please indicate which window(s) meets the requirements of IBC
1031 for Emergency Escape and Rescue Openings for each sleeping room and resubmit for review. The window
schedule does not address this.
10/13/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 10/9/2025 7:11:32 PM
1. E0.5 ELECTRICAL EXTERIOR LIGHTING CUTSHEETS & COMCHECK: Missing interior lighting comcheck.
2. E3.0 ENLARGED ELECTRICAL LIGHTING PLAN - LEVEL 1: Missing an interior lighting comcheck for this specific
area.
3. E3.1 ENLARGED ELECTRICAL POWER PLAN - LEVEL 1: Could not locate Keyed Note 22.
4. E3.2 ENLARGED ELECTRICAL FLOOR PLANS: Keyed Note 11 calls out design location of Media panel to be under
the electrical panel. This violates NEC 110.26(E) code requirements for dedicated working space of power panels.
Space directly above and below the power panel are reserved for circuits to enter into the power panel and cannot be
obstructed by any panels or equipment that cannot function as a raceway for circuits entering or leaving the power
panel. A low voltage media panel does not meet this requirement and therefore cannot be mounted below the power
panel. Relocate media panel to another location.
5. E4.0 ELECTRICAL ONE-LINE DIAGRAM: Confirm underground primary requirement for (9) 4” conduits. The primary
side of a medium voltage transformer typically only requires a couple of feeders.
6. E4.1 ELECTRICAL PANEL SCHEDULES: Trip rating in SES-HP for Panel P2A should be 100 amps as per One-Line
on sheet E4.0.
7. E4.2 ELECTRICAL PANEL SCHEDULES: Comment only, Multi-Meter Load Calculations could have used 26% as per
NEC Table 220.84.
10/13/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 10/6/2025 1:18:01 PM
1. General - Plan Sheet M1.0 & M2.0 FCU A-1 total CFM at the supply air grills/diffusers ais 766 CFM. Plan Sheet M0.2
states on the VARIABLE REFRIGERANT FLOW FAN COIL UNIT SCHEDULE for FCU A-1 "Supply Fan Airflow
(CFM) 625. Confirm Total CFM for FCU A-1 at the Supply air grills/diffusers. - 2018 IECC Section C103.2Information
on construction documents - 2018 IBC Section [A]107.2.1Information on construction documents.
2. General - Plan Sheet M2.0 FCU B-1 total CFM at the supply air grills/diffusers ais 1550 CFM. Plan Sheet M0.2 states
on the VARIABLE REFRIGERANT FLOW FAN COIL UNIT SCHEDULE for FCU B-1 "Supply Fan Airflow (CFM) 2000.
Confirm Total CFM for FCU B-1 at the Supply air grills/diffusers. - 2018 IECC Section C103.2Information on
construction documents - 2018 IBC Section [A]107.2.1Information on construction documents.
3. General - Plan Sheet M1.2 FCU A-3 total CFM at the supply air grills/diffusers ais 796 CFM. Plan Sheet M0.2 states
on the VARIABLE REFRIGERANT FLOW FAN COIL UNIT SCHEDULE for FCU A-3 "Supply Fan Airflow (CFM) 625.
Confirm Total CFM for FCU A-3 at the Supply air grills/diffusers. - 2018 IECC Section C103.2Information on
construction documents - 2018 IBC Section [A]107.2.1Information on construction documents.
4. General - Provide refrigerant routing on plans. Provide riser details - 2018 IECC Section C103.2Information on
construction documents - 2018 IBC Section [A]107.2.1Information on construction documents.
5. General - A2L type refrigerants require ASHRAE 15 calculations for each type design using A2L type refrigerants.
Refrigerant shafts vented (naturally or mechanically) may be required when routing refrigerant lines through floors.
Monitoring systems with alarms may also be required. - 1109.3 Installation requirements for A2L and B2L
refrigerants. 1109.2.5 Refrigerant pipe shafts. 1109.3.2 Shaft ventilation. 1109.2.4 Piping in concrete floors. 1109.5
Refrigerant pipe penetrations .1109.8.1 Refrigerating systems containing more than 6.6 pounds (3.0 kg) of refrigerant.
1109.3.3 Pipe identification. 1109.3.1 Pipe protection. ASHRAE 15 and ASHRAE 34. - 2018 IMC - 2018 IECC Section
C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction documents.
10/13/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 10/12/2025 2:36:13 PM
First Plumbing Review:
1). Plan Page P3.0 details 2,4,5,6,7: The Waste Stack/Vent must remain full size thru roof. Edit the Waste Stack/Vent size to
remain the same size or lager as it originates at the ground thru the roof level. -2018 IPC 913.3, 913.4
10/15/2025 Fire New Construction Standard REQUIRES RESUBMIT 1. Sheet T2.0, applicable codes. COT/TFD has adopted the 2024 IFC. Please make correction to your applicable codes.
2. Please make a note that the fire alarm will be installed in accordance with IFC 907.2.9 and NFPA 72.
3. Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
10/07/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-0925-01751
Location: 855 W Prince RD
Review Date: 10/7/2025
Site Engineering Comments:
1. Site Engineering will be unable to review and approve permit TC-COM-0925-017451until the associated development package TD-DEV-0925-00236 is reviewed and approved by all reviewers.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
10/24/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0925-01751
855 W. Prince Rd. Tucson, AZ 85705
3 Story Apartment Building (1st Review)

TRANSMITTAL DATE: 10/24/2025

The site is in the C-2 zone (UDC 4.7.21). Multifamily is a permitted use in the C-2 zone.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Zoning has conducted a cursory review of the building permit and while it appears the site plan is consistent with the development package, Site Zoning cannot approve this building permit until the associated development package (TD-DEV-0924-00246) has been approved by all reviewers. We are requiring a revision to TD-DEV-0924-00246 as this project will be reviewed as one site. Please ensure the building plans provided match what is being reviewed in the development package revision.
2. Comment: Additional comments may be forthcoming based on responses to zoning comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
09/25/2025 PDSD Application Completeness Express REVIEW COMPLETED