Permit Number: TC-COM-0925-01750
Parcel: 117120210

Address:
9 N SCOTT AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0925-01750
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2025 Commercial Mechanical Standard APPROVED
12/03/2025 Design Review Standard NOT REQUIRED Narrative on first page of plans indicate no modifications to the exterior of the building are being proposed.
12/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/28/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
N1. The interior exit stairway discharges into a lobby and that is not allowed with only one exit. It is conditionally allowed under Exceptions for not more than 50 percent of the occupants.
IBC 1028.1. Exits shall discharge directly to the exterior of the building. The exit discharge shall be at grade or shall provide a direct path of egress travel to grade. The exit discharge shall not reenter a building.
This means the interior exit stairway exit discharge needs to exit directly outside. For example, the addition of an exterior door to be added.
N2. Please amend the plans to show 1.5-hour fire resistive rated doors as required by IBC Table 716.1(2) The stairway is described as having 1-Hour rated doors and these do not meet minimum code requirements.
N3. Please amend the plans to remove or otherwise address the doors from the interior exit stairway that allow egress back into the building, as exit discharge should be to the exterior. IBC 1028.1
N4. The door leading to the basement stairway appears to reduce the egress width by more than one-half and does not meet IBC 1005.7.1 requirements. Please amend the plans accordingly.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
11/28/2025 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0925-01750
ADDRESS/PARCEL: (9 N SCOTT AV TUCSON, AZ 85701)
COMMENTS:

1. Previous comment not addressed. I am not able to find the prefabricated shower receptor listed on the Architectural sheets. Please specify the prefabricated shower receptor and clearly call it out on the drawings.
12/02/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
PDSD Zoning Review Section

PROJECT:
TC-COM-0925-01750
9 N. Scott Ave. Tucson, AZ 85701
Existing building/first floor retail remodel into Bakery/Mezzanine and second floor office remodel adding bathrooms (2nd Review)

TRANSMITTAL DATE: 12/2/2025

Comment: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

This site is located in the OCR-2 zone (UDC 4.7.27).

1. Comment: Follow up to previous comment 1. Bakery is not a defined use in the Unified Development Code. A bakery is classified as either Perishable Goods Manufacturing or Food and Beverage Sales. If the use is classified as Perishable Goods Manufacturing (accessory use to the principal use of the building), please clearly define the principal use of the site/building and any accessory uses. Please also include square footage and percentages for each use. Please refer to UDC Table 4.8-4 if necessary.
2. Comment: Follow up to previous comment 2. This site is located within the COT Downtown Core and Rio Nuevo Area (RNA), RNA review must be completed prior to zoning approval. Please contact Maria Gayosso at Maria.Gayosso@tucsonaz.gov if you have questions about the RNA review process.
3. Comment: Additional comments may be forthcoming based on responses to zoning comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
11/25/2025 Commercial Building Standard REVIEW COMPLETED
11/28/2025 Fire New Construction Standard REVIEW COMPLETED
11/05/2025 PDSD Application Completeness Express REVIEW COMPLETED