Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0925-01745
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/13/2025 | Commercial Electrical Standard | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 10/8/2025 5:10:26 PM |
||
| 10/08/2025 | Outdoor Lighting Standard | APPROVED | |||
| 10/22/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/13/2025 | Commercial Building Standard | REQUIRES RESUBMIT | Structural(S) Reviewer Andrew Bevis abevis@safebuilt.com Denied Reason: Date Completed : 10/13/2025 9:58:53 AM 1. GENERAL/GEOTECHNICAL REPORT: Please provide a copy of the site-specific geotechnical report for this project. The report should support the appropriateness of the selected foundation system for the project site. [All submitted geotechnical reports must be dated no later than three years from the submittal date. - AREA SPECIFIC] Outdated reports must be accompanied by a letter from a qualified geotechnical engineer stating that the report requirements are still valid, or stating what items may have changed. All building code references must be updated to the current code adopted by the City of Tucson. 2. GENERAL/STRUCTURAL CALCULATIONS: No structural calculations have been provided. Please provide the structural calculations for this project. Building(B) Reviewer Andrew Frame aframe@safebuilt.com Denied Reason: Date Completed : 10/9/2025 3:45:15 PM 10/09/2025 Review Requires Resubmittal AFrame: 1) Sheet T1.0: Please provide completed Building and Mechanical COMcheck, and resubmit for review. 2) Sheet E5.0: Per 1013 2018 IBC-Exit Signs: Please show location of emergency lights and resubmit for review. 3) Sheet E5.0: Per 1008.3.5 2018 IBC-Illumination level under emergency power: Please show location of emergency lights and resubmit for review. |
||
| 10/13/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 10/6/2025 12:10:07 PM 1. General - Plan Sheet M4.0 Details #5 and #7 Show single nut on the roof and hood attachments. Confirm with manufacture installation instructions double nut requirements are not needed. - 2018 IECC Section C103.2Information on construction documents - 2018 IBC Section [A]107.2.1Information on construction documents. |
||
| 10/13/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 10/4/2025 10:08:17 PM First Plumbing Plan Review: 1). Plan Page P6.0: Missing required backflow devices at each beverage device. Add required backflow devices at each beverage device. -2018 IPC 608.17.1 2). Plan Page P1.0: Missing TMV-1 info. Add TMV-1 Info. -2018 IPC 419.5 3). Plan Page P1.0: Missing Primary & Secondary Roof Drain info. Add Primary & Secondary Roof Drain info.. -2018 IPC 1102.6 4). Plan Page P2.0: Missing Primary & Secondary Roof Drain piping sizes & GPM Loads. Add Missing Primary & Secondary Roof Drain piping sizes & GPM Loads. - 2018 IPC 1106.2 |
||
| 10/14/2025 | Fire New Construction Standard | REQUIRES RESUBMIT | -COT/TFD has adopted the 2024 IFC. Make correction to sheet T1.0, adopted codes. -Sheet T1.0 indicates a fire alarm will be installed. Verify a fire alarm will be installed. If no fire alarm, remove the note. -CO2 systems for beverage dispensing >100lbs of CO2 require a CO2 gas detection alarm. IFC 5307.3. -Resolve all building comments. john.vincent@tucsonaz.gov 5203495581 |
||
| 10/06/2025 | Site Engineering Standard | REQUIRES RESUBMIT | Permit: TC-COM-0925-01745 Location: 495 E WETMORE RD Review Date: 10/6/2025 Site Engineering Comments: 1. Site Engineering will be unable to review and approve permit TC-COM-0925-01745 until the associated development package TD-DEV-0825-00216 is reviewed and approved by all reviewers. If you have any questions or concerns, please contact Marco Contreras Marco.contreras@tucsonaz.gov |
||
| 10/22/2025 | Site Zoning Standard | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Ramiro Olivarez Zoning Review Section PROJECT: TC-COM-0925-01745 - TD-DEV-0825-00216 495 E WETMORE RD – C-3 Zoning Food Service (1st Review) TRANSMITTAL DATE: 10/22/2024 COMMENTS: Please resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. Comment: Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-0624-00169. Until the DP is approved by all review agencies Zoning cannot approve this building plan. 2. Comment: The building SF is larger than what is listed on Development Package TD-DEV-0825-00216 general notes. Correct Building SF to match. 3. Comment: Additional comments may be forthcoming on the next review based on the proposed use and applicable use specific standards. If you have any questions about this transmittal, please contact Ramiro Olivarez Ramiro.Olivarez@tucsonaz.gov |
||
| 10/15/2025 | Water - PDSD Standard | REQUIRES RESUBMIT | Provide the size of the proposed water meter, the size of the backflow preventer associated with the water meter, and the total water demand to be served by the water meter. Reference: Section 107.2.1, IBC 2018. | ||
| 09/24/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |