Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0925-01745
Parcel: 105102440

Address:
495 E WETMORE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0925-01745
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2025 Commercial Electrical Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 10/8/2025 5:10:26 PM
10/08/2025 Outdoor Lighting Standard APPROVED
10/22/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/13/2025 Commercial Building Standard REQUIRES RESUBMIT Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 10/13/2025 9:58:53 AM
1. GENERAL/GEOTECHNICAL REPORT: Please provide a copy of the site-specific geotechnical report for this project.
The report should support the appropriateness of the selected foundation system for the project site. [All submitted
geotechnical reports must be dated no later than three years from the submittal date. - AREA SPECIFIC] Outdated
reports must be accompanied by a letter from a qualified geotechnical engineer stating that the report requirements
are still valid, or stating what items may have changed. All building code references must be updated to the current
code adopted by the City of Tucson.
2. GENERAL/STRUCTURAL CALCULATIONS: No structural calculations have been provided. Please provide the
structural calculations for this project.



Building(B) Reviewer
Andrew Frame
aframe@safebuilt.com
Denied
Reason:
Date Completed : 10/9/2025 3:45:15 PM
10/09/2025 Review Requires Resubmittal AFrame:
1) Sheet T1.0: Please provide completed Building and Mechanical COMcheck, and resubmit for review.
2) Sheet E5.0: Per 1013 2018 IBC-Exit Signs: Please show location of emergency lights and resubmit for review.
3) Sheet E5.0: Per 1008.3.5 2018 IBC-Illumination level under emergency power: Please show location of emergency lights
and resubmit for review.
10/13/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 10/6/2025 12:10:07 PM
1. General - Plan Sheet M4.0 Details #5 and #7 Show single nut on the roof and hood attachments. Confirm with
manufacture installation instructions double nut requirements are not needed. - 2018 IECC Section C103.2Information
on construction documents - 2018 IBC Section [A]107.2.1Information on construction documents.
10/13/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 10/4/2025 10:08:17 PM
First Plumbing Plan Review:
1). Plan Page P6.0: Missing required backflow devices at each beverage device. Add required backflow devices at each
beverage device. -2018 IPC 608.17.1
2). Plan Page P1.0: Missing TMV-1 info. Add TMV-1 Info. -2018 IPC 419.5
3). Plan Page P1.0: Missing Primary & Secondary Roof Drain info. Add Primary & Secondary Roof Drain info.. -2018 IPC
1102.6
4). Plan Page P2.0: Missing Primary & Secondary Roof Drain piping sizes & GPM Loads. Add Missing Primary & Secondary
Roof Drain piping sizes & GPM Loads. - 2018 IPC 1106.2
10/14/2025 Fire New Construction Standard REQUIRES RESUBMIT -COT/TFD has adopted the 2024 IFC. Make correction to sheet T1.0, adopted codes.
-Sheet T1.0 indicates a fire alarm will be installed. Verify a fire alarm will be installed. If no fire alarm, remove the note.
-CO2 systems for beverage dispensing >100lbs of CO2 require a CO2 gas detection alarm. IFC 5307.3.
-Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
10/06/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-0925-01745
Location: 495 E WETMORE RD
Review Date: 10/6/2025
Site Engineering Comments:
1. Site Engineering will be unable to review and approve permit TC-COM-0925-01745 until the associated development package TD-DEV-0825-00216 is reviewed and approved by all reviewers.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
10/22/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Ramiro Olivarez
Zoning Review Section

PROJECT: TC-COM-0925-01745 - TD-DEV-0825-00216
495 E WETMORE RD – C-3 Zoning
Food Service (1st Review)

TRANSMITTAL DATE: 10/22/2024

COMMENTS: Please resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Comment: Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-0624-00169. Until the DP is approved by all review agencies Zoning cannot approve this building plan.

2. Comment: The building SF is larger than what is listed on Development Package TD-DEV-0825-00216 general notes. Correct Building SF to match.

3. Comment: Additional comments may be forthcoming on the next review based on the proposed use and applicable use specific standards.

If you have any questions about this transmittal, please contact Ramiro Olivarez Ramiro.Olivarez@tucsonaz.gov
10/15/2025 Water - PDSD Standard REQUIRES RESUBMIT Provide the size of the proposed water meter, the size of the backflow preventer associated with the water meter, and the total water demand to be served by the water meter. Reference: Section 107.2.1, IBC 2018.
09/24/2025 PDSD Application Completeness Express REVIEW COMPLETED