Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/23/2025 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0925-01713 (198 S GRANADA AV TUCSON, AZ 85701)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide updated plans showing compliance to the currently adopted codes, NEC 2017, ICC 2018. Cannot submit previously stamped plans from 2006.
3. Provide an electrical plan showing any/all electrical work.
Plans shall include, but may not be limited to items below:
4. Provide a line diagram showing the new equipment being added or modified, NEC 110.2, 2018 IBC 107.1.
5. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2017 NEC 110.24.
6. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/22/2025 PDSD Application Completeness Express REVIEW COMPLETED