Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0925-01706
Parcel: 130083440

Address:
3456 E 27TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0925-01706
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/23/2025 Commercial Plumbing Express REQUIRES RESUBMIT 1 Provide construction documents created by a licensed plumbing contractor. Reference: Section 107.2.1, IBC 2018
2 Revise the natural gas pipe replacement drawing to show:
1. The location of the gas meter
2. The gas load for each piece of equipment in BTUH
3. The developed pipe length from the meter to each piece of equipment
4. The size and material of each pipe segment.
Reference: Section 107.2.1, IBC 2018.
09/19/2025 PDSD Application Completeness Express REVIEW COMPLETED