Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0925-01706
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/23/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/23/2025 | Commercial Plumbing Express | REQUIRES RESUBMIT | 1 Provide construction documents created by a licensed plumbing contractor. Reference: Section 107.2.1, IBC 2018 2 Revise the natural gas pipe replacement drawing to show: 1. The location of the gas meter 2. The gas load for each piece of equipment in BTUH 3. The developed pipe length from the meter to each piece of equipment 4. The size and material of each pipe segment. Reference: Section 107.2.1, IBC 2018. |
||
| 09/19/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |