Permit Number: TC-COM-0925-01686
Parcel: 105110690

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0925-01686
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2025 Commercial Building APPROVED
09/26/2025 Commercial Electrical APPROVED
10/07/2025 Site Zoning APPROVED
09/29/2025 Water - PDSD APPROVED
10/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/29/2025 Commercial Mechanical REQUIRES RESUBMIT 1. Provide detail 107, noted on sheet M1. Reference: Section 107.2.1, IBC 2018.
2. Verify that the proposed kilns are listed and labeled as complying with UL 499. Provide the manufacturer’s installation instructions. Reference: Section 923, IMC 2018.
3. Identify the quantities of glazes and other finishing materials that will be stored (closed and open) or in use. Provide the safety data sheets for the materials and identify the manufacturer’s precautionary statements (e.g. ventilation requirements).
4. Identify any proposed spraying operations of the glazes.
09/29/2025 Commercial Plumbing REQUIRES RESUBMIT Verify that the architect understands that the point-of-use water dispenser specified in the plumbing fixture schedule is approved as a substitute for a water fountain while the “bottle drinking fountain” is not an acceptable sole substitute for a water fountain.
09/30/2025 Fire New Construction REVIEW COMPLETED