Permit Number: TC-COM-0925-01685
Parcel: 123080560

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0925-01685
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2025 Commercial Building APPROVED
10/07/2025 Site Zoning APPROVED Interior TI Only
10/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/29/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0925-01685 (2725 E SPEEDWAY BL TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. On Sheet E-1.0, Electrical (N) Work Plan there are callouts for receptacles tied to circuits that are shown as ‘Spare’ on the electrical panel schedule (34,26 & 38,40). Please correct these circuit callouts.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/30/2025 Commercial Mechanical REQUIRES RESUBMIT The compounding room contains five exhaust hoods with undisclosed exhaust flow rates, operating schedules, and unknown exhaust fans. Provide specifications for the hood exhaust system(s) and verify that the proposed room pressure controls will be able to maintain the proposed relative room pressure range.
09/30/2025 Commercial Plumbing REQUIRES RESUBMIT Show how the two hot water recirculation branches will be balanced. Reference: Section 107.2.1, IBC 2018.
09/29/2025 Fire New Construction REQUIRES RESUBMIT -Sheet SD1.0, code review #8, states fire sprinkler and fire alarm required. I do not have records of fire sprinklers or fire alarm at this location. Are you installing these fire protection systems?
-Sheet SD1.0, applicable codes. COT/TFD has already adopted the 2024 IFC. Please update code.
-Include exiting/life safety plan showing exits, travel distance, etc...
john.vincent@tucsonaz.gov
5203495581
09/17/2025 PDSD Application Completeness Express REVIEW COMPLETED