Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/16/2025 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0925-01681 (3232 E 4TH ST Unit:UNIT 5 TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Clarify if this is a service upgrade or if the service size remains the same.
2. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2017 NEC 110.24.
3. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov