Permit Number: TC-COM-0925-01671
Parcel: 10706110A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0925-01671
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/02/2025 Commercial Building Standard APPROVED
10/17/2025 Commercial Mechanical Standard NOT REQUIRED
10/02/2025 Fire New Construction Standard NOT REQUIRED
09/19/2025 Site Engineering Standard NOT REQUIRED
10/16/2025 Site Zoning Standard NOT REQUIRED
10/17/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/29/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0925-01671 (2918 N EL BURRITO AV TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide a Panel A with a rating greater than the minimum load as calculated per NEC 408.30.
2. Provide a Panel A with a rating greater than the 600A OCPD shown on the one-line diagram, NEC 408.36. Panel A is rated at 400A.
3. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2017 NEC 110.24. >>> Panel A shows an AIC rating of only 10kA.
4. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov