Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0925-01664
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/25/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/25/2025 | Commercial Mechanical Express | REQUIRES RESUBMIT | 1. Comment not addressed. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018. 2. Comment not addressed. [Initial comment: Verify that the existing natural gas piping system is capable of supplying the new gas-fired equipment. Provide a piping layout showing the pipe sizes, loads, pressure regulators, and developed lengths of the piping before and after the pressure regulators. Reference: Section 107.2.1, IBC 2018. |
||
| 09/23/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |