Permit Number: TC-COM-0925-01664
Parcel: 105110710

Address:
4374 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0925-01664
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/15/2025 Commercial Mechanical Express REQUIRES RESUBMIT 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018.
2. Verify that the existing natural gas piping system is capable of supplying the new gas-fired equipment. Provide a piping layout showing the pipe sizes, loads, pressure regulators, and developed lengths of the piping before and after the pressure regulators. Reference: Section 107.2.1, IBC 2018.
09/11/2025 PDSD Application Completeness Express REVIEW COMPLETED