Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2025 Commercial Building APPROVED
09/22/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/12/2025 Commercial Electrical REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0925-01640 (2436 N 1ST AV TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Outdoor Lighting Review:

1. Add the following notes
“24 hour programmable timer installed to comply with the COT Outdoor Lighting Code.
The means of controlling the specific “off” curfew shall be by a 24 hour timing device that includes stand-by power to maintain the time and program for a minimum of 6 hours. OLC 403.5 & 501.6. “ Timer shall be set to 11:00PM per OLC 501.2.


Provide permanent curfew “off” time sign or notice:
2. Whenever any curfew “off” time is required by this Code, a permanent sign or notice shall be installed at the time control device stating the required turn-off time. Such sign or notice may be installed within the cover of the time control device such that it is visible whenever the device is set or adjusted, OLC 403.5.2.
Suggested wording is as follows: “Set off time for Sign no later than 10:00PM MST in accordance with City of Tucson/Pima County Outdoor Lighting Code. Penalty for non-compliance per Outdoor Lighting Code Section 107.4. Penalties shall not exceed $750.00 for individuals and $10,000.00 for other legal entities.” (Adjust wording as needed for type of lighting to which curfew applies and the applicable curfew time.)


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/12/2025 Outdoor Lighting REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0925-01640 (2436 N 1ST AV TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. The timer device cannot be placed withing the service panel as this would violate the panel’s listing, NEC 110.3(B). The timing device does not meet the requirements of NEC 312.8 to be placed within the panelboard.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/22/2025 Signs REQUIRES RESUBMIT September 18. 2025
2436 N. 1st Ave. - TC-COM-0925-01640; COT 465
Repair Permit Application
Comments:
1. The thickness of the existing and proposed plywood panels is not noted.
The thickness must be "like for like".
2. On Sheet 4 of 4, the One-Line Diagram identifies a "Crouse Hinds
Disconnect" that is to be replaced with a new 122 Panel. The disconnect is
not noted on the elevation of the 'Electrical Service (Exist.)" Please verify
what is being removed and what is being installed in its place.
3. Also on the One-Line Diagram, it looks like a total of eight light fixtures are
being reinstalled, yet the "New Panel A" identifies two light fixtures per side
for a total of four fixtures. Does the One-Line show actual bulbs (2 per
fixture?). Please confirm which is correct.
Kathi McLaughlin, BRC Reviewer
09/22/2025 Site Zoning REQUIRES RESUBMIT Refer to Sign comments.
09/08/2025 PDSD Application Completeness Express REVIEW COMPLETED