Permit Number: TC-COM-0925-01623
Parcel: 11103080E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0925-01623
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2025 Commercial Electrical APPROVED
09/23/2025 Site Zoning APPROVED
09/23/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/19/2025 Commercial Building REQUIRES RESUBMIT 1. Sheet T-0.0: Please amend the Building Code List to include the following. IBC 107.2.1
2018 International Existing Building Code (IEBC)
2009 ICC A117.1 Accessibility Code (by reference)
2024 International Fire Code (IFC)
2018 International Energy Conservation Code (IECC)
City of Tucson/Pima County Outdoor Lighting Code
Local Amendments to Above Codes ( www.tucsonaz.gov/pdsd/building-codes )
2. Sheet T-0.0: Please amend the Index of drawings to include Sheet E300 and remove E200 as the last sheet. IBC 107.1
3. Sheet T-0.0: Please verify and amend the Use Group to include all the Use designations for the Occupancy Classification of B. IBC 302.2 For example, this space appears to include group therapy, accessible showers, medical dispensing room, etc. (Outpatient Clinic)
A. Please provide a copy of your State of Arizona license or the application if the license is being processed. IBC 107.2.1
4. Please amend the plans to add a detailed description of the work involved in this permit scope of work on the plans. IBC 105.3
5. Sheet A-1.0: Please amend plans to provide a legend or provide complete names in the room descriptions. IBC 107.1 For example, IOP, MAT room
6. Sheet A-1.0: Please amend plans to indicate the heights of all counter tops, reception/ service counters, showing clear floor space and front or parallel approach. 2009 ICC A117.1 Chapter 8 Treat this as a typical note for all accessible elements in this project.
7. Please amend plans to include an architectural site plan showing accessible parking space and exterior accessible route to the accessible entrance. IBC 107.2.6
8. Sheet A-1.0: Please amend plans to indicate the path(s) of exit discharge gates have only egress door equivalent hardware. IBC 1010.2
9. Sheet A-1.0: Please amend plans to name the type of accessible shower (transfer, roll-in and alternate roll-in) and include dimensioned interior elevations locating controls, benches, etc., and an enlarged dimensioned floor plan of the accessible shower showing compliance with 2009 ICC A117.1 608.1
10. Sheet A-1.0: Please amend plans to show any built-in furniture, appliances and tables. IBC 107.2.1
11. Sheet A-1.0: Please amend plans to show the following.
A. The number of occupants is shown for every room and space. IBC 107.2.3
B. The occupant load factor and area are shown for every room and space. IBC 1004.5
C. The occupant load factor used reflects the use/function of the space. IBC 1004.5
12. Sheet A-1.0: Please amend plans to show approach, as the maneuvering distance of 60 inches is required for front approach at Door 7. 2009 ICC A117.1 TABLE 404.2.3.2—Maneuvering Clearances at Manual Swinging Doors
13. Sheet A-1.0: Please amend plans to show approach, and the clear floor space for the 25” pass thru counter in MAT room #131. 2009 ICC A117.1 Chapter 9 & 904.3.2


Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
09/18/2025 Commercial Mechanical REQUIRES RESUBMIT Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018.
09/18/2025 Commercial Plumbing REQUIRES RESUBMIT 1. Specify the cycle time for the metering faucets. The metering faucets shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. If the shower does not have a prefabricated receptor, provide details to show that the construction of the receptor complies with the requirements of Section 421.5, IPC 2018.
3. For the use of PEX tubing, provide a branch tube sizing chart showing the correct size of PEX tubing to be used as a substitute for the copper pipe shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2018.
4. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
09/18/2025 Water - PDSD REQUIRES RESUBMIT Provide the size of the water meter serving this building. Based on the calculated water demand, a ¾” or larger water meter is required. Reference: Section 107.2.1, IBC 2018.
09/17/2025 Fire New Construction REVIEW COMPLETED
09/04/2025 PDSD Application Completeness Express REVIEW COMPLETED