Permit Number: TC-COM-0925-01621
Parcel: 133170630

Address:
350 N WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0925-01621
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/26/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0925-01621
ADDRESS/PARCEL: 350 N WILMOT RD TUCSON, AZ 85711
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov
COMMENTS:

1. The most recent file uploaded does not include the information for the ductless AC unit and condensate drain. Please upload the revised file that includes these updates. Please see previous comments below.
a. Provide the specifications for the ductless AC unit (e.g. manufacturer, model number, heating/cooling capacity, and efficiency ratings). The unit shall have an efficiency rating that is greater than or equal to the minimum required by the Department of Energy that went into effect on January 1, 2023.
b. Show the size, routing, and termination of the condensate drain from the ductless AC unit. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
03/06/2026 PDSD Application Completeness Express REVIEW COMPLETED