Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0925-01621
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/18/2025 | Commercial Electrical Standard | APPROVED | |||
| 09/30/2025 | Site Zoning Standard | APPROVED | |||
| 09/26/2025 | Commercial Building Standard | NOT REQUIRED | |||
| 09/25/2025 | Fire New Construction Standard | NOT REQUIRED | |||
| 09/17/2025 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 09/16/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 09/30/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/25/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Provide the specifications for the ductless AC unit (e.g. manufacturer, model number, heating/cooling capacity, and efficiency ratings). The unit shall have an efficiency rating that is greater than or equal to the minimum required by the Department of Energy that went into effect on January 1, 2023. 2. Show the size, routing, and termination of the condensate drain from the ductless AC unit. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson. |
||
| 09/04/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |