Permit Number: TC-COM-0925-01621
Parcel: 133170630

Address:
350 N WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0925-01621
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2025 Commercial Electrical Standard APPROVED
09/30/2025 Site Zoning Standard APPROVED
09/26/2025 Commercial Building Standard NOT REQUIRED
09/25/2025 Fire New Construction Standard NOT REQUIRED
09/17/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
09/16/2025 Site Engineering Standard NOT REQUIRED
09/30/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/25/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide the specifications for the ductless AC unit (e.g. manufacturer, model number, heating/cooling capacity, and efficiency ratings). The unit shall have an efficiency rating that is greater than or equal to the minimum required by the Department of Energy that went into effect on January 1, 2023.
2. Show the size, routing, and termination of the condensate drain from the ductless AC unit. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
09/04/2025 PDSD Application Completeness Express REVIEW COMPLETED