Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0925-01619
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/29/2026 | Commercial Building Standard | APPROVED | |||
| 01/14/2026 | Site Engineering Standard | APPROVED | |||
| 01/28/2026 | Site Zoning Standard | APPROVED | Approved with TD-DEV-0924-00245 | ||
| 01/29/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/29/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov Both the development plan and plumbing plan now show a ¾” water meter and a 1” water service to building 22. The development plan, however, now shows a ¾” backflow preventer while the plumbing plan shows a 1” backflow preventer. Coordinate the drawings. [Initial comment: Verify the size of the water service to the building and the backflow preventer. The development plan shows a 2” water service and a 2” backflow preventer while the site plan and plumbing plan show a 1” water service and a 1” backflow preventer. Reference: Section 107.2.1, IBC 2018.] |
||
| 01/07/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |