Permit Number: TC-COM-0925-01617
Parcel: 14111002D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0925-01617
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2025 Commercial Electrical Standard APPROVED
09/24/2025 Commercial Mechanical Standard APPROVED
09/15/2025 Outdoor Lighting Standard APPROVED
09/24/2025 Water - PDSD Standard APPROVED
09/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/24/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please amend plans to name the Accessible Entrances and the Accessible Exits and provide Signage as required by IBC 1111.1
2. Provide a drawing detail or otherwise indicate the door, threshold, and landing are accessible. 2009 ICC A117.1 Chapter 4

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
09/24/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Provide specifications for the “utility sink with bottle filler per owner” noted on sheet P1.0. The use of a point-of-use water dispenser in lieu of a drinking fountain requires the installation of a listed and labeled water dispenser along with a permanently mounted disposable cup dispenser. The cup dispenser shall be located adjacent to the water dispenser with the dispensing end between 34” and 48” above the finished floor. See: https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/2008-21_e_drinkingfountainpolicy.pdf
2. Verify the size of the water service to the building and the backflow preventer. The development plan shows a 2” water service and a 2” backflow preventer while the site plan and plumbing plan show a 1” water service and a 1” backflow preventer. Reference: Section 107.2.1, IBC 2018.
3. Clarify the material to be used for the water service pipe. It appears that you will be using Type K soft-drawn copper. Reference: Section 107.2.1, IBC 2018.
4. Clarify the material you will be using for the above ground water piping. What is “TYPE ANGLE HARD DRAWN COPPER”? Reference: Section 107.2.1, IBC 2018.
5. An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer (i.e., 30” from the exterior walls of the building); otherwise, cleanouts shall open to allow cleaning only in the direction of flow. Reference: Section 708.1.8, IPC 2018.
6. The plumbing plan shows a different, longer route for the building sewer from the building to the private sewer connection than the site plan. Coordinate the two drawings and verify that a maximum of 100’ developed length is between cleanouts.
7. The rim elevation of the next upstream sanitary manhole (2864.9) is higher than the first-floor elevation (2862.60). Provide a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
09/16/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-0925-01617
Location: 8300 E VALENCIA RD Unit:BLDG 23
Review Date: 9/16/2025
Site Engineering Comments:
1. The Commercial building plans call for 6000 SQ FT, but the Development package TD-DEV-0924-00245 shows that each proposed building is 4000 SQ FT, this will require a revision to the development package before the commercial permit TC-COM-0925-01617 can move forward.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
09/29/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0925-01617
8300 E. Valencia Rd. Tucson, AZ 85747; I-1
A-Family Storage Valencia Bldg 23 (1st Review)

TRANSMITTAL DATE: 9/29/2025

This site is zoned I-1 (UDC 4.7.29).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: The associated approved Development Package (TD-DEV-0924-00245) lists the building square footage as 4,000 sf however the building plan lists the square footage as 6,000 sf. The dimensions provided on the development package need to match the associated building permit. Either revise the square footage to match the approved Development Package or revise TD-DEV-0924-00245 to match the associated building plans.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
09/23/2025 Fire New Construction Standard REVIEW COMPLETED
09/03/2025 PDSD Application Completeness Express REVIEW COMPLETED