Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0925-01612
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/18/2025 | Water - PDSD | NOT REQUIRED | |||
| 09/22/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/19/2025 | Commercial Building | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0925-01612 ADDRESS/PARCEL: (2343 N RALPH AV TUCSON, AZ 85712) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. COMMENTS: 1. TWO DWELLING UNITS INVOLVED. a. Unit 2343 i. This permit (TC-COM-0925-01612), the City will continue using this permit for unit 2343. ii. Thank You for submitting the structural engineer’s inspection and suggested remedies for the identified damages. iii. Provide a Floor Plan. On the floor plan, identify the damages. iv. Provide drawings illustrating/depicting the suggested solutions and fixes. v. Ensure to provide drawings corresponding to the items on the fire damage report. vi. Provide detail drawings such as the wall replacement, detail wall drawing at the furred wall, if party walls are damaged and needing repair… provide drawings that illustrate what is being installed to comply to the fire rating requirement from floor to underside of the roof sheathing. vii. Are the bathroom and kitchen cabinets being removed and replaced. viii. Are the kitchen appliances being replaced. Notate this on your drawings. ix. Are any of the doors being replaced as a result of the fire damage. x. Are the alarm system damaged. Show on your drawing if any of the smoke detectors are being replaced (show on your drawings by labeling them and their location and their status). b. Unit 2341 i. Each unit must have their own building permit. ii. Please submit a separate building permit application for Unit 2341. iii. Please submit the same items as listed within Unit 2343 above. 2. Please resubmit. Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976 |
||
| 09/11/2025 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0925-01612 (2343 N RALPH AV TUCSON, AZ 85712) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf 2. Provide an electrical plan showing any/all electrical work. Plans shall include, but may not be limited to items below: 3. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40. 4. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4. 5. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1. 6. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 09/18/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Provide construction documents that are complete and clearly indicate the extent of the proposed work. The plans shall have sufficient detail and demonstrate that the work complies with the applicable codes. Any mechanical equipment being replaced (e.g., heat pumps, exhaust fans, etc.) shall comply with the current codes for energy efficiency The plans shall be sealed by an Arizona Registrant. Reference: Section 107.2.1, IBC 2018. | ||
| 09/18/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Provide construction documents that are complete and clearly indicate the extent of the proposed work. The plans shall have sufficient detail and demonstrate that the work complies with the applicable codes. Any plumbing fixtures being replaced shall be listed, labeled, and installed in accordance with their listing. The plans shall be sealed by an Arizona Registrant. Reference: Section 107.2.1, IBC 2018 and Section 303, IPC 2018. | ||
| 09/22/2025 | Site Zoning | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Ramiro Olivarez Zoning Review Section PROJECT: TC-COM-0925-01612 2343 N RALPH AV – R-2 Zoning Fire Unit repairs (1st Review) TRANSMITTAL DATE: 09/22/2025 COMMENTS: Please resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. Comment: See and address Commercial Building Review comments. 2. Comment: Include a floor plan and identify the damages. 3. Comment: Additional comments may be forthcoming on the next review based on the proposed use and applicable use specific standards. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Corrected Building Plans. If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov |
||
| 09/04/2025 | Fire New Construction | REVIEW COMPLETED | |||
| 09/04/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |