Permit Number: TC-COM-0925-01606
Parcel: 11108313D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0925-01606
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2025 Site Zoning Standard NOT REQUIRED
09/23/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide a detailed description of the work and the location of each guardrail replacement and indicate the scope of the stucco repair. IBC 107.2.1 For example, guardrail repair, Unit 100, 101, 105, 109 etc., or indicate all guardrails to be replaced.
2. Please provide construction drawings and construction details showing the guardrail repair including connections, and the stucco repair(s) and indicate the materials to be used for both of the repairs. IBC 107.2.1
3. Please date the seal on the drawings. AZBTR and COT Commercial Submittal Requirements.

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
09/19/2025 Fire New Construction Standard REVIEW COMPLETED
09/03/2025 PDSD Application Completeness Express REVIEW COMPLETED