Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0924-01878
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/03/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/03/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide overcurrent protection for existing panelboard ‘L1’ as required per NEC art 408.36(B). 2 Provide a complete panel schedule for panel ‘L1’. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
09/30/2024 | PDSD Application Completeness | REVIEW COMPLETED |