Permit Number: TC-COM-0924-01877
Parcel: 12709011M

Address:
335 N WILMOT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0924-01877
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2024 Commercial Electrical APPROVED
10/10/2024 Commercial Plumbing NOT REQUIRED
10/14/2024 Site Engineering NOT REQUIRED
10/07/2024 Site Zoning NOT REQUIRED
10/14/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/10/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please provide a sealed evaluation report or statement from an Arizona licensed engineer verifying the existing roof structure will be able to resist the additional load of the new rooftop condensing units. INC 107.2.7

2. Please provide detailed drawings and calculations to show the attachment of the new units to the existing roof structure to resist any wind loads. IBC 107.2.1
3. Please provide a list of special inspections required for the fasteners used to secure the rooftop units to the roof structure. IBC 1007.4
4. Please provide a special inspection form with parts A and B completed with the next submittal. IBC 107



Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
10/10/2024 Commercial Mechanical REQUIRES RESUBMIT Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
10/07/2024 Fire New Construction REVIEW COMPLETED
09/27/2024 PDSD Application Completeness REVIEW COMPLETED