Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0924-01866
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/28/2024 | Water - PDSD | APPROVED | |||
| 10/28/2024 | Site Engineering | NOT REQUIRED | |||
| 10/30/2024 | Site Zoning | NOT REQUIRED | |||
| 10/30/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/24/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide an electric lighting plan that shows all lighting modifications and lighting controls, including Emergency lighting for egress and Surgery room. . See LIGHTING NOTES A, B, and C on plan sheet ‘E1’. Include 2018 IECC compliance. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
| 10/28/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Is EF-4, scheduled for the pet operating room actually EF-6? Reference: Section 107.2.1, IBC 2018. | ||
| 10/28/2024 | Commercial Plumbing | REQUIRES RESUBMIT | The plans show an indirect waste receptor being covered by the installation of a clothes washing machine which will prevent ready access to the waste receptor. Relocate or remove the indirect waste receptor. Reference: Section 802.4, IPC 2018. | ||
| 10/28/2024 | Commercial Structural | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0924-01866 ADDRESS/PARCEL: (2661 N 1ST AV TUCSON, AZ 85719) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. COMMENTS: 1. KENNEL ROOM: New wall is built very close to the kennel cages, so much so that circulation width would not comply. Please confirm if this was an oversight, please correct to comply. 2. INDUSTRIAL WASHER & DRYER ROOM: There is some type of equipment (I think) that is present within the space impeding access width not compliant. Is this a left over from the existing layer? Please correct making sure the access width are code compliant. 3. Please resubmit. |
||
| 10/24/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 09/27/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |