Permit Number: TC-COM-0924-01866
Parcel: 107132690

Address:
2661 N 1ST AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0924-01866
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2024 Water - PDSD APPROVED
10/28/2024 Site Engineering NOT REQUIRED
10/30/2024 Site Zoning NOT REQUIRED
10/30/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/24/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide an electric lighting plan that shows all lighting modifications and lighting controls, including Emergency lighting for egress and Surgery room. . See LIGHTING NOTES A, B, and C on plan sheet ‘E1’. Include 2018 IECC compliance.

Ref; 2018 IBC section 107.2.1, 2017 NEC.
10/28/2024 Commercial Mechanical REQUIRES RESUBMIT Is EF-4, scheduled for the pet operating room actually EF-6? Reference: Section 107.2.1, IBC 2018.
10/28/2024 Commercial Plumbing REQUIRES RESUBMIT The plans show an indirect waste receptor being covered by the installation of a clothes washing machine which will prevent ready access to the waste receptor. Relocate or remove the indirect waste receptor. Reference: Section 802.4, IPC 2018.
10/28/2024 Commercial Structural REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0924-01866
ADDRESS/PARCEL: (2661 N 1ST AV TUCSON, AZ 85719)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. KENNEL ROOM: New wall is built very close to the kennel cages, so much so that circulation width would not comply. Please confirm if this was an oversight, please correct to comply.
2. INDUSTRIAL WASHER & DRYER ROOM: There is some type of equipment (I think) that is present within the space impeding access width not compliant. Is this a left over from the existing layer? Please correct making sure the access width are code compliant.
3. Please resubmit.
10/24/2024 Fire New Construction REVIEW COMPLETED
09/27/2024 PDSD Application Completeness Express REVIEW COMPLETED