Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0924-01858
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/04/2024 | Commercial Electrical | APPROVED | |||
11/05/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/05/2024 | Commercial Mechanical | REQUIRES RESUBMIT | The required source-capture exhaust inlet is located at the end of a four-foot long table . It is more likely that the operator and client will be situated about two feet from the exhaust grille, too far from the exhaust grille to effectively capture the chemical fumes. Revise the exhaust inlet to ensure that the intake is located a maximum of 12” from the point of chemical application. [Initial comment: Nail salons require a source-capture exhaust system for each manicure station. The exhaust inlets shall be located a maximum of 12” horizontally and 12” vertically from the point of chemical application. Provide a detail showing how this is to be accomplished. Reference: Table 403.3.1.1, footnote h and Section 502.20, IMC 2018.] | ||
10/22/2024 | PDSD Application Completeness | REVIEW COMPLETED |