Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0924-01853
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/18/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Keynote 4 on sheet P20-02 does not address the maximum distance of the heat source to the lavatory faucet. If a new hot water recirculation system is to be installed, both the hot water supply and the hot water return pipes shall be insulated per Section C403.5.3, IECC 2018. [Second comment: Per Table C404.5.1, IECC 2018, the maximum distance from the heat source (e.g. a hot water recirculation loop) to the public lavatory faucet is 2 feet with a ½” supply (6 feet if you insist on using a ¼” supply). See Detail 2/P01-02 for a good example of how to plumb a lavatory in a public restroom and coordinate your hot water supply design and your keynotes on sheet P20-02.] [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] | ||
| 12/17/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |