Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW REVISION v.2
Permit Number - TC-COM-0924-01847
Review Name: COMMERCIAL PDSD SIMPLE REVIEW REVISION v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/13/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/13/2025 | Commercial Electrical Fast | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0924-01847 (6408 E TANQUE VERDE RD TUCSON, AZ 85715) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. You cannot use previously Sealed documents, even with the Seal removed. Please submit a new and original diagram showing the installation of the TEP required 5th jaw. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 02/13/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |