Permit Number - TC-COM-0924-01830
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/24/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/24/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Show the locations of the existing electrical service ‘SES-R’ and the new panel ‘LB4’ on the electrical site plan and floor plan. 2 Provide for the ‘Common Grounding Electrode’ requirements per NEC 250.58 for all the electrical services serving the same building. 3 Provide an electrical floor plan showing locations for all equipment and devices supplied by the new panel ‘LB4’ and equipment and devices associated with the new ‘UPS’. Assign branch circuits and panels for all equipment and devices shown on the floor plans. 4 Provide compliance with NEC 517.13 where applicable. 5 Keynote #6 shown at the MRI Chiller (Line Diagram) makes reference to plan sheet ‘ep102’ for additional information. Plan sheet ‘ep102’ cannot be located in the plan set. Please clarify. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||