Permit Number: TC-COM-0924-01816
Parcel: 11504505A

Review Status: Requires Resubmit

Review Details: COMMERCIAL POOLS v.1

Permit Number - TC-COM-0924-01816
Review Name: COMMERCIAL POOLS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/26/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
12/26/2024 Commercial Building REQUIRES RESUBMIT September 30, 2024
1st Review

Ankrom Moisan
Attn: Jason Jones
38 NW Davis Street
Portland, OR 97209

Re: CAPSTONE
SWIMMING POOL

City of Tucson Permit Number: TC-COM-0924-01816
Stantec Project Number: 185215066
Stantec File Number: TUC-24-132

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-4 I-A 612 30 Yes Yes
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet SP1.02

1. Please provide the landscape plans referenced on this sheet to verify barrier compliance of the pool enclosure. [Ref. AAC R18-5-240]

2. Please indicate that the windows serving the dwelling units that surround the pool will be equipped with a screwed-in place wire mesh screen or keyed lock that prevents opening the window more than 9 inches. [Ref. AAC R15-5-240 F-1]

3. Please indicate all doors leading to the swimming pool will have the release mechanism of the self-latching device be located at least 54 inches above the floor. [Ref. AAC R18-5-240-F-2]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
10/02/2024 Site Zoning REQUIRES RESUBMIT Until Development Package (DP) TD-DEV-0324-00107 is approved by all review agencies Zoning cannot approve the pool permit,
09/24/2024 PDSD Application Completeness REVIEW COMPLETED