Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0924-01813
Parcel: 105110710

Address:
4368 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0924-01813
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
09/24/2024 Commercial Mechanical REQUIRES RESUBMIT Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). Reference: Section C503.4, IECC 2018.
09/19/2024 PDSD Application Completeness REVIEW COMPLETED