Permit Number: TC-COM-0924-01808
Parcel: 124150180

Address:
960 E 17TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0924-01808
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2025 Commercial Mechanical APPROVED
05/20/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/20/2025 Commercial Electrical REQUIRES RESUBMIT
04/25/2025 Commercial Plumbing REQUIRES RESUBMIT 1. Sheet P4 Plan identifies two gas water heaters. Will need to provide Combustion air, venting and vent termination details for review. Incomplete on plans 2018 IBC 107.2.1.
2. WH-2 has been removed from scope of work. New WH-1 is identified as gas. CA & Venting have not been identified on plans. Note plumbing typical detail 201 on sheet P5 identifies an electric WH
04/25/2025 Commercial Structural REQUIRES RESUBMIT For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179
1. sheet c0.01 Plan sheet m2.0 identified in index is missing from plans. will need to provide in new plan set. 2018 IBC 107.2.1 (BM)
2. Sheet g1.01 Provide for review, cooler wall panel types, anchoring, ceiling panels and closure requirements. 2028 IBC 107.2.1 (BM)
3. Revised plans have removed one walk-in cooler. Cooler in scope of work area is still pending data in plans or identified as a deferred submittal
4. Sheet S2.0 CU & EC for walkin coolers are identified on sheet E1.0 to be on the roof. Clarify any additional support requirements. 2018 IBC 107.2.1 (BM)
5. One walk-in cooler has been removed from plan. No response has been provided addressing remaining new equipment on new kitchen area.
05/05/2025 Fire New Construction REVIEW COMPLETED Kitchen fire suppression system requires a separate submittal and permit. CO2 System requires an operational permit (If applicable)
04/24/2025 PDSD Application Completeness Express REVIEW COMPLETED