Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0924-01808
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2024 | Site Zoning | APPROVED | I-1: Commercial Kitchen (Perishable Good Manufacturing) subject to UDC 4.9.5.C.2, .4, .5, .6, .8, 4.9.5.E.1 & .2 and 4.9.13.Q | ||
| 10/15/2024 | Water - PDSD | APPROVED | |||
| 10/21/2024 | Site Engineering | NOT REQUIRED | |||
| 10/22/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/01/2024 | Commercial Electrical | REQUIRES RESUBMIT | 1. Sheet e2.0 Will need to provide an EM egress light at stairs from dock to comply with 2018 IBC 1008.3.2 Incomplete (BM) | ||
| 10/22/2024 | Commercial Mechanical | REQUIRES RESUBMIT | |||
| 10/01/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Sheet P2 Detail 224 at cooler is not identified on sheet P6, Clarify. 2018 IBC 107.2.1 (BM) 2. Sheet P2 Plans identify Existing WH next to WH-2, clarify if in use or out of service. 2018 IBC 107.2.1 (BM) 3. Sheet P4 Plan identifies two gas water heaters. Will need to provide Combustion air, venting and vent termination details for review. Incomplete on plans 2018 IBC 107.2.1 |
||
| 10/01/2024 | Commercial Structural | REQUIRES RESUBMIT | C0.01 For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. All applicable comments followed by the initials (BM) 1. Sheet c0.01 Both building area SF and kitchen area SF exceed requirements for Business Group B occupancy classification per 2018 IBC 304.1. Max 2500 SF or less for commercial kitchens not associated with restaurant or dinning facilities. Over 2500 SF is a Group F-1 (BM) Note: provide a design analysis for other occupancy or mixed occupancy 2. Sheet c0.01 Provide list of deferred submittal items on plan sheet. Incomplete per 2018 IBC 107.3.4.1 (BM) 3. Sheet g1.00 Building egress plan does not appear to have an accessible route into or for exiting to comply with 2018 IBC 1009.1 (BM) 4. Sheet g1.00 Kitchen 2 is identified with ramps and a stair at the three door openings. Provide existing or new landing dimensions, ramp dimensions and slopes, guards, handrail and tread and riser to comply with 2018 IBC 1011 & 1012. (BM) 5. Sheet g1.01 Provide for review, cooler wall panel types, anchoring, ceiling panels and closure requirements. 2028 IBC 107.2.1 (BM) 6. Sheet a1.03 Identify on plans new gyp board ceiling support. Provide details and data for suspended GB ceiling system if not fastened directly to ceiling / roof structure. Not clear on plans. 2018 IBC 107.2.1 (BM) 7. Sheet a1.05 Provide on door schedule all existing door sizes, types, locks and hardware to comply with 2018 IBC section 1010.1 Incomplete (BM) Note: all door levers/ latches are to be ADA compliant. 8. Sheet S2.0 CU & EC for walkin coolers are identified on sheet E1.0 to be on the roof. Clarify any additional support requirements. 2018 IBC 107.2.1 (BM) |
||
| 10/15/2024 | Fire New Construction | REQUIRES RESUBMIT | -Resolve all building comments. john.vincent@tucsonaz.gov 5203495581 |
||
| 09/20/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |