Permit Number: TC-COM-0924-01761
Parcel: 11706081G

Address:
410 N TOOLE AV

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - TC-COM-0924-01761
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2025 Water Sterilization Report (Deferred Submittal) Express APPROVED
03/12/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/10/2025 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT The revise air balance report shows that the outside air flow rate is still 23% below the requirement. [Initial comment: The air balance report shows that the existing fan coil unit does not provide the required ventilation for the assembly occupancy. Revise the plans as needed to provide the necessary outside airflow to the space. Reference: Sections 401.2 and 401.3, IMC 2018.]
03/12/2025 County Health Inspection (Deferred Submittal) Express REVIEW COMPLETED
03/07/2025 PDSD Application Completeness Express REVIEW COMPLETED