Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0924-01761
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/27/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/27/2025 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | 1. The air balance report shows that the existing fan coil unit does not provide the required ventilation for the assembly occupancy. Revise the plans as needed to provide the necessary outside airflow to the space. Reference: Sections 401.2 and 401.3, IMC 2018. 2. The existing restroom exhaust fan does not move sufficient air to comply with the engineer’s design. Evaluate the situation and determine a course of action to provide adequate ventilation for the restroom. Reference: Section 403.3.1.1 and Table 403.3.1.1, IMC 2018. |
||
| 02/26/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |