Permit Number: TC-COM-0924-01761
Parcel: 11706081G

Address:
410 N TOOLE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0924-01761
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/17/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
12/11/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Provide the gas delivery pressure at the meter (e.g., 7” WG, 2 PSIG, or 5 PSIG) and the developed pipe length from the meter to the water heater. Reference: Sections 402.1 and 402.3, IFGC 2018.
2. The specified tankless water heater will produce 8.9 GPM of hot water with a temperature rise of 80°F and it has a maximum flowrate of 13.2 GPM. The pressure drop across the water heater is over 25 PSI at 13.2 GPM. The calculated hot water demand for your system is approximately 16 GPM: how will a single tankless water heater satisfy the hot water demand? Consult the manufacturer’s instructions for designing the hot water system. Reference: Section 303.2 and 604.3, IPC 2018.
3. Unless the existing restroom has an independent source of hot water, both lavatories will need to have a maximum distance of 24” from the circulating hot water loop. Provide a means of balancing the hot water flow to the branches serving the lavatories in the public restrooms or modify the system to have only one hot water circulation loop. Reference: Section 404.5, IECC 2018.
12/17/2024 Design Review REVIEW COMPLETED Interior only, design review not required.
11/26/2024 PDSD Application Completeness REVIEW COMPLETED