Permit Number: TC-COM-0924-01750
Parcel: 10123516B

Address:
3742 W RIVER RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0924-01750
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/07/2025 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 2/4/2025 1:09:52 PM
1. (UNRESOLVED) - General - Provide Heat Load Calculations. Heat Load Calculations must match Design on plans. -
2018 IECC Section C403.1.1 Calculation of heating and cooling loads.
i. Grease Hood plans show a 2288 CFM KEF (Kitchen Exhaust Fan). Show on the Heat Load calculations the
makeup air CFM heat load. Ventilation calculations are not stating the KEF CFM. - 2018 IECC Section
C403.1.1 Calculation of heating and cooling loads. - 2018 IBC – Section [A]107.2.1Information on construction documents. - 2018 IECC Section C103.2Information on construction documents.
ii. Provide an Air Balance schedule. - 2018 IMC Section 508.1.1 Makeup air temperature. - 2018 IMC Section 508.1.2 Air Balance


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 2/6/2025 8:43:09 PM
02/03/2025 PDSD Application Completeness Express REVIEW COMPLETED